Model selection (e.g:ESR□ -4A2B-E)

Panel function

Application Details
Safetyrelay expansion module ESR-4A2B-E supply4 safetycontacts output and 2 auxiliary output in safety circuit. Connect A1 of ESR-4A2B-E to output terminal of the previous device,A2 connected the pole of power supply, when previous device send rightsignal, the related contacts ofexpansion module has corresponding action.|
Functional diagram

Automatic reset
●ESRE-4A2B: Connect A1,A2 of ESRE-4A2B as diagram, when previous device output active signal, the component works.
●Input circuit output active signal to ESRE-4A2B, K1 & K2 of relay get energized and held, indicator CH1, CH2 light up, safety contacts 13-14/23-24/33-34/43-44 close, and auxiliary Y1-Y2/ 51-52 contacts open.
Safety feedback loop
● Connect YS, Y2 in series to feedback loop of previous device, when a related fault occurs, the safety relay expansion module will not perform the corresponding action.
● The input circuit is disconnected (The input circuit has no valid signal output to the safety relay expansion module), relay K1, K2 are disconnected, indicator light CH1, CH2 are off, safety contacts 13-14/23-24/33-34/43-44 are disconnected, andauxiliary contacts Y1-Y2/51-52 are closed.
Product Installation
 |
 |
Installation diagram |
Removal diagram |
Carefully read the manual before installation, and ensure power supply is cut off when wiring.Wiring with power is prohibited.