Safety Relay Module

Brand: ESPE 

Model: ESR Series

Product Feature:

1. Design according to ISO13849-1 (category 3, Ple);

2. Relay output: 2NO or 3NO, and 1 NC auxiliary contact;

3. Optional manual reset and automatic reset;

4. Self-diagnose and redundant circuit design;

5. Standard 35mm width guide mounting design.

 

 

Product Details

Parameter of safety relay module

Standard level
Reference standard ISO 13849-1(Category 4/Pl e)
Safety level Category 4/ Pl e
Electric parameter
Supply voltage DC24V±10%
Power consumption <3W
Response time <20ms
Suction buffer time <100ms
Power-on restart time <1s
Protective circuit Input power overvoltage protection, anti-reverse protection
Safety input Double NPN normally closed input (ESRN type), double PNP normally closed input (ESRP type); Dual door or emergency stop button (ESRS type)
Input synchronously Unlimited S1 is in the front of S2
Safety output 2 normally open passive contacts,1 normally closed passive contacts; Three normally open passive contacts and one normally closed passive contact;
B10 data Rated load: 400,000 times; Low load: 2 million times
Contacting rating AC15: 5A/250V; DC13: 6A/24V
Electric lifespan ≥10 times(1NO: 5A250VAC, resistive load, 1s on 9s off)
Mechanical lifespan ≥10 millions times
 Environment
Vibration resistance Frequency 10Hz~55Hz, amplitude 0.35±0.05mm, 20 times each at X, Y, Z direction
Impact resistance Acceleration 10g, pulse duration 16ms, X, Y and Z direction 1000 times each
Operational temperature -25ºC~+60ºC
Storage temperature -40ºC~+85ºC
Protection level Shell / terminal protection: IP40/IP20
Installation/structure
Installation 35mm Rail
Traverse size 0.2~2.5mm²
Size (mm) 117 x 100.6 x 22.5

 

Model selection (e.g: ESR□ -3A1B-E)

 

Product Size

 

Product installation

● Cut off power of machine toensure no dangerous voltage existing, except the lighting and spare sockets.

● Product with35mmDIN rail for installation.

● Connect wire according to the wiring diagram of the safety relay.

● Before power on, please check if all cable rightly connected,and whether relay is fastened to the mounting rail.

 

 

Disassemble

● Please cut off power before disassembling the safety module.

● Loosen the screw or remove terminal.

 

 

Panel function

ESR(N/P)-2A1B-E

ESR(P/N/S)-3A1B-E

 

 

Functional diagram

ESR(N/P)-2A1B-E

 

ESR(N/P)-3A1B-E

 

ESRS-3A1B-E

 

 

Wiring diagram

ESRN/P-2A1B-E used for safety light curtain (manual reset/ automatic reset)

 

ESR(N/P)-3A1B-E used for safety door switch (NPN/PNP output)

 

Used for safety light curtain (NPN/PNP output)

 

Used for dual channel safety door

 

Used for emergency stop button